Washington's crawl space rules
Washington writes its own crawl space requirements into the state residential code at WAC 51-51-0408. They apply in Tukwila under the State Building Code.
Ground cover. Under WAC 51-51-0408, the soil must be covered with six-mil black polyethylene or an approved equal, lapped 6 inches at joints and extended to the foundation wall.
Vents. Under the same section, the minimum net vent area is 1 square foot for every 300 square feet of crawl space, with vent coverings whose openings are no larger than a quarter inch.
Reduced vents. The code adds that where the ground is covered with a Class I vapor retarder, the vent area may drop to 1 square foot per 1,500 square feet, provided cross ventilation is kept. Venting below 1 per 300, or fitting operable louvers, requires a radon vent.
No vents. An unvented crawl space under WAC 51-51-0408 is allowed where the exposed earth has a continuous Class I vapor retarder, with joints overlapped 6 inches and sealed and edges carried 6 inches up the stem wall and sealed, plus a radon system to the code's Appendix AF, and where continuously operated mechanical exhaust runs at 1 cubic foot per minute for every 50 square feet of floor, ending outside. The rule's one exception is an existing structure used as a supply plenum under M1601.5. Unlike the national model code, Washington lists no conditioned-air or dehumidifier option in place of the exhaust. The text doesn't say outright whether both conditions are always required together, so the City's building official confirms how it applies to a given house.